The
910 Emergency Module provides a complete system lock down at
the flip of a switch. It is used in the AES 900 Door Control
System, using the 900 or 905 Door Control Rack.
The 910 Module can be used in conjunction with any number
of doors connected to 940 or 945 control modules. In an emergency,
the operator can lock all doors - even overriding an UNLOCK
condition caused by input from a fire control. The operator
can then open the doors one at a time, or all at
once as the situation dictates.
Rack Location: Must be located in first (left-most) position.
Lock Down Module Operation
• Switch in Down Position - Normal Operation; in the
event of a fire, the external fire control system will unlock
all doors
• Switch in Up Position - Emergency Lock Down; all doors
are locked regardless of any other inputs; overrides fire
control
To Open Doors During Emergency Lockup (910
switch in UP position):
• To Open Individual Door(s): On each 940 and/or 945
module, lift guard and move toggle switch into UP position
• To Cancel Emergency Lockup: Restore switch on 910
to DOWN (normal) position
• Fire Doors with 946 Status Display Panel (at door):
use key switch at door to release lock